Dry Contact card for FLIX
Potential-free contact card providing signals indicating the operating status of the power supply
Compatibility: FLIX
15-DKFL-AS400
Product features
- The card provides potential-free contacts for remote monitoring of UPS operation status
- Input contact for UPS shutdown operation
Contact definition
PIN | Sygnalizacja | Rodzaj styku | Opis |
1 | UPS fault | Output | Open from common connection: UPS is abnormal. Closed: UPS is normal. |
2 | General alarm | Output | Open from common connection: UPS is warning Closed: UPS is normal |
3 | GND | GND | Internal GND, used to connect external power supply 12-24Vdc |
4 | Remote shutdown | Input | Input port. Used with external power supply. If connected to power supply, UPS transfer to bypass. UPS shutdown if bypass is abnormal. |
5 | Common connection | Common | Common connection of output signal. Connected to power supply for input signal. |
6 | Bypass mode | Output | Closed to common connection: UPS is working in bypass mode Open: UPS is not working in bypass mode. |
7 | Battery low | Output | Open from common connection: battery low alarm Closed: battery capacity is normal or not in battery mode |
8 | Normal mode | Output | Closed from common connection: UPS is working in normal mode. |
9 | Utility failure | Output | Open from common connection: utility input fails. |
- Card type
- Dry contact card