COVER Online Double-Conversion uninterruptible power supply, with a capacity of 10kVA/10kW.  3:3/3:1 phase configuration.

Number of batteries: 120 x 9Ah

11-Z-JR 10K-340009

Essential accessories

Accesories

Communication

AUTONOMY TIME

JR 10KLoadAutonomy time [min]
80 x 9Ah100%47.7
75%64.4
50%131.4
25%248.6


CHARACTERISTICS

  • True OnLine technology True On-Line Double Conversion technology ensures excellent output voltage performance regardless of power interference and the type of loads being powered.
  • IGBT rectifier The most advanced technology providing very low THDi and high power factor.
  • Bypass automatyczny Uninterruptible power supply provides uninterrupted power to consumers in critical situations like overheating or failure.
  • Service bypass allows servicing of equipment without shutting down the powered loads. Separate power supply of the Bypass track gives the possibility to provide a backup power source for the consumers even in case of equipment failure or UPS protection tripping in the main track.
  • Communication interfaces:
  • - USB, RS232, IntelliSlot for monitoring and managing the operation of the power supply and receivers,
  • - DryContact relay contacts for interfacing with BMS systems
  • - SNMP integration with NMS-type network management systems
  • - Remote Emergency Power Off (REPO) connector. (REPO) for providing remote disconnection of power to consumers in the event of a fire,
  • - The Fire Protection Switch. (EPO) on the control panel allows you to immediately disconnect power to loads,
  • 4.3" LCD color touchscreen control and monitoring panel simplifies UPS operation, allows diagnostics of parameters and operating mode of the power supply, and enables event logging.
  • Small dimensions The UPS has the ability to install batteries internally, so no additional space is needed for basic backup times.
  • Very efficient charging system makes the UPS capable of quickly charging battery banks with very large capacities, for long autonomous operation times.
  • High efficiency of the device (>96%) reduces the emitted heat, making the eventual cooling of the premises simpler and the UPS much cheaper to operate.
  • ECO-Mode allows a significant reduction in the cost of operation of the device and virtually eliminates the emission of heat.
  • Automatic diagnostics and digital control (32 bit DSP x2) guarantees full device performance, control of components and operating parameters without user intervention.
  • High value of input power factor 0.99 limits the value of the current drawn by the device from the grid.
  • Highest output power factor value 1.0 allows the power supply to be loaded with full active power.
  • Wide input voltage range in normal operation mode ensures stable operation of the device without the need for batteries, which significantly extends their life.
  • Wide input frequency range in normal operation mode allows the power supply to be used freely in a network with unstable parameters and when powered by a generator set.
  • Ease of use The ease of connection to the network and the simple switching on and off of the device does not require special qualifications from the user.
  • Advanced battery management guarantees optimal charging and utilization of battery banks, increases battery life and reduces operating costs. Temperature compensation function of charging voltage.
  • Excellent output voltage quality achieved through the use of a 3-level IGBT inverter, with the use of advanced PWM control technology makes it possible to deliver a voltage with stable parameters, regardless of energy disturbances and the type of powered devices.
  • High overload capacity Ensures protection of the device and continuity of power supply in the presence of transient transients.
  • Advanced software enabling the user to have full control over the device and the powered loads.
  • Configurability of operating parameters nominal voltages, frequencies, preferred modes of operation, method of communication - greatly expands the range of possible applications.
  • Redundant configurations:
  • - Redundant parallel operation for increased reliability
  • - Capacitive parallel operation for increased power
  • - HotStandby work


TECHNICAL SPECIFICATIONS

ModelJR 10K
Power factor10kVA / 10kW
Phases In/Out3:3 / 3:1
DesignTower
Input
Nominal voltage380 / 400 / 415 Vac
Voltage range-53% ÷ +30% @ 50% load
-24% ÷ +20% @ 100% load
Nominal frequency50 / 60Hz
Frequency range-20% ÷ +20%
THDi<3%
Input power factor≥0,99
Output
Nominal voltage380 / 400 / 415 VAC lub 220 / 230 / 240 VAC
Power factor1,0
Voltage regulation statis/dynamic±1% / ±2%
Nominal frequency50 / 60 ± 0,05 Hz
Overload caability110% - 60 min., 125% - 10 min., 150% - 60 s
Short circuit capability340% of nominal curent by 200 ms
Efficiency in OnLine mode>96%
Efficiency in ECO mode>99%
Crest factor3:1
Switching time0ms
Batteries
Cold startyes
Type of batteriesVRLA, AGM, gel
Batteries range16 - 20 pcs x 12V
Max quantity of internal batteries40 x 9Ah/12V
Max charging curent12A
Charging type3 – 8 hours up to 90% capacity (configurable)
Charging cycleAccording to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control.
Dimensions and weights
Dimensions (S x G x W)250 x 627 x 827mm
Weight w/o batteries44,0 kg
Weight with batteries154,0 kg
Signaling and communication ports
Operating status indicatorLCD + audible alarm
CommunicationUSB, RS232, IntelligentSlot, REPO, EMBS, parallel port
Optional: SNMP, ModBus, DryContact, RS485
Environmental conditions
Noise level<58 dB @ load 100%, <52 dB @ load 50%
Operating temperature for UPS0°C ÷ 40°C
Recommended operating temperature15 °C ÷ 25 °C
Storage temperature-20°C ÷ 40°C
Humidity0 ÷ 95% (non-condensing)
Cerifications
Interference immunityEN62040-2:2016
SafetyEN62040-1:2017, EN62040-3:2011, CE
Optional accesories
- SNMP card
- RS485 (Modbus) card
- AS 400 mini (dry-contact) card
- Environmental sensor (EMD)
- Remote Emergency Power Off button
- External maintenance bypass
- Backfeed protection
- Parallel cables
- Remote LCD panel

Due to constant product improvement all specifications are subject to change without notice.

Apparent power [kVA]
10
Active power [kW]
10
Technology:
VFI-SS-111 (OnLine DoubleConversion)
Phase In/Out:
3:3
Output PF:
1
Max internal batteries
40
Backup time under 100% load
30 - 60 minutes

Related Products ( 16 other products in the same category )