• Pack
UPS COVER JR 15K - 46 min.

UPS COVER JR 15K - 46 min.

COVER Online Double-Conversion uninterruptible power supply, 15kVA/15kW. 3:3/3:1 phase configuration.

Number of batteries: 40 x 45Ah

11-Z-JR 15K-140045

Essential accessories

Accesories

Communication

AUTONOMY TIME

JR 15 Load Autonomy time [min]
40 x 45Ah 100% 46.0
75% 68.9
50% 104.1
25% 282.9

CHARACTERISTICS

  • True OnLine technology True On-Line Double Conversion technology ensures excellent output voltage performance regardless of power interference and the type of loads being powered.
  • IGBT rectifier The most advanced technology providing very low THDi and high power factor.
  • Automatic bypass Uninterruptible power supply provides uninterrupted power to consumers in critical situations like overheating or failure.
  • Service bypass allows servicing of equipment without shutting down the powered loads. Separate power supply of the Bypass track gives the possibility to provide a backup power source for the consumers even in case of equipment failure or UPS protection tripping in the main track.
  • Communication interfaces:
  • - USB, RS232, IntelliSlot for monitoring and managing the operation of the power supply and receivers,
  • - DryContact relay contacts for interfacing with BMS systems
  • - SNMP integration with NMS-type network management systems
  • - Remote Emergency Power Off (REPO) connector. (REPO) for providing remote disconnection of power to consumers in the event of a fire,
  • - The Fire Protection Switch. (EPO) on the control panel allows you to immediately disconnect power to loads,
  • 4.3" LCD color touchscreen control and monitoring panel simplifies UPS operation, allows diagnostics of parameters and operating mode of the power supply, and enables event logging.
  • Small dimensions The UPS has the ability to install batteries internally, so no additional space is needed for basic backup times.
  • Very efficient charging system makes the UPS capable of quickly charging battery banks with very large capacities, for long autonomous operation times.
  • High efficiency of the device (>96%) reduces the emitted heat, making the eventual cooling of the premises simpler and the UPS much cheaper to operate.
  • ECO-Mode allows a significant reduction in the cost of operation of the device and virtually eliminates the emission of heat.
  • Automatic diagnostics and digital control (32 bit DSP x2) guarantees full device performance, control of components and operating parameters without user intervention.
  • High value of input power factor 0.99 limits the value of the current drawn by the device from the grid.
  • Highest output power factor value 1.0 allows the power supply to be loaded with full active power.
  • Wide input voltage range in normal operation mode ensures stable operation of the device without the need for batteries, which significantly extends their life.
  • Wide input frequency range in normal operation mode allows the power supply to be used freely in a network with unstable parameters and when powered by a generator set.
  • Ease of use The ease of connection to the network and the simple switching on and off of the device does not require special qualifications from the user.
  • Advanced battery management guarantees optimal charging and utilization of battery banks, increases battery life and reduces operating costs. Temperature compensation function of charging voltage.
  • Excellent output voltage quality achieved through the use of a 3-level IGBT inverter, with the use of advanced PWM control technology makes it possible to deliver a voltage with stable parameters, regardless of energy disturbances and the type of powered devices.
  • High overload capacity Ensures protection of the device and continuity of power supply in the presence of transient transients.
  • Advanced software enabling the user to have full control over the device and the powered loads.
  • Configurability of operating parameters nominal voltages, frequencies, preferred modes of operation, method of communication - greatly expands the range of possible applications.
  • Redundant configurations:
  • - Redundant parallel operation for increased reliability
  • - Capacitive parallel operation for increased power
  • - HotStandby work

TECHNICAL SPECIFICATIONS

Model JR 15K
Power factor 15kVA / 15kW
Phases In/Out 3:3 / 3:1
Design Tower
Input
Nominal voltage 380 / 400 / 415 Vac
Voltage range -53% ÷ +30% @ 50% load
-24% ÷ +20% @ 100% load
Nominal frequency 50 / 60Hz
Frequency range -20% ÷ +20%
THDi <3%
Input power factor ≥0,99
Output
Nominal voltage 380 / 400 / 415 VAC lub 220 / 230 / 240 VAC
Power factor 1,0
Voltage regulation statis/dynamic ±1% / ±2%
Nominal frequency 50 / 60 ± 0,05 Hz
Overload caability 110% - 60 min., 125% - 10 min., 150% - 60 s
Short circuit capability 340% of nominal curent by 200 ms
Efficiency in OnLine mode >96%
Efficiency in ECO mode >99%
Crest factor 3:1
Switching time 0ms
Batteries
Cold start yes
Type of batteries VRLA, AGM, gel
Batteries range 32 - 40 pcs x 12V
Max quantity of internal batteries 40 x 9Ah/12V
Max charging curent 12A
Charging type 3 – 8 hours up to 90% capacity (configurable)
Charging cycle According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control.
Dimensions and weights
Dimensions (S x G x W) 250 x 627 x 827mm
Weight w/o batteries 44,0 kg
Weight with batteries 154,0 kg
Signaling and communication ports
Operating status indicator LCD + audible alarm
Communication USB, RS232, IntelligentSlot, REPO, EMBS, parallel port
Optional: SNMP, ModBus, DryContact, RS485
Environmental conditions
Noise level <58 dB @ load 100%, <52 dB @ load 50%
Operating temperature for UPS 0°C ÷ 40°C
Recommended operating temperature 15 °C ÷ 25 °C
Storage temperature -20°C ÷ 40°C
Humidity 0 ÷ 95% (non-condensing)
Cerifications
Interference immunity EN62040-2:2016
Safety EN62040-1:2017, EN62040-3:2011, CE
Optional accesories
- SNMP card
- RS485 (Modbus) card
- AS 400 mini (dry-contact) card
- Environmental sensor (EMD)
- Remote Emergency Power Off button
- External maintenance bypass
- Backfeed protection
- Parallel cables
- Remote LCD panel

Due to constant product improvement all specifications are subject to change without notice.

Apparent power [kVA]
15
Active power [kW]
15
Technology:
VFI-SS-111 (OnLine DoubleConversion)
Phase In/Out:
3:3
Output PF:
1
Max internal batteries
40
Backup time under 100% load
30 - 60 minutes

Related Products ( 16 other products in the same category )