UPS COVER CORE 6K
COVER Online Double-Conversion uninterruptible power supply, with 6kVA/6kW. Rack/Tower (2U) cabinet. 1:1 phase configuration.
11-CORE-0060
CHARACTERISTICS
|
|
BACKUP TIME
EBM CORE 6/10K | Load | Backup time [min] |
CORE 6K | ||
UPS + 1xEBM (20x9Ah) | 100% | 8.4 |
75% | 12 | |
50% | 22.1 | |
25% | 52.8 | |
UPS + 1xEBM (20x7Ah) | 100% | 4.7 |
75% | 8.0 | |
50% | 14.6 | |
25% | 32.2 | |
UPS + 2xEBM (2x20x9Ah) | 100% | 22.1 |
75% | 32.1 | |
50% | 52.7 | |
25% | 144.2 | |
UPS + 2xEBM (2x20x7Ah) | 100% | 14.6 |
75% | 21.1 | |
50% | 32.1 | |
25% | 83.4 | |
UPS + 3xEBM (3x20x9Ah) | 100% | 37.7 |
75% | 52.7 | |
50% | 89.6 | |
25% | 202.3 | |
UPS + 3xEBM (3x20x7Ah) | 100% | 23.6 |
75% | 32.1 | |
50% | 59.1 | |
25% | 137.8 | |
UPS + 4xEBMS (4x20x9Ah) | 100% | 52.7 |
75% | 72.8 | |
50% | 143.8 | |
25% | 292.5 | |
UPS + 4xEBMS (4x20x7Ah) | 100% | 32.1 |
75% | 50.0 | |
50% | 83.1 | |
25% | 203.6 |
TECHNICAL SPECIFICATIONS
Model | CORE 6K |
Power | 6kVA / 6,0kW |
Phases In/Out | 1:1 |
Input | |
Nominal voltage | 208 / 220 / 230 / 240 Vac |
Voltage range | 100 ÷ 300 Vac |
Nominal frequency | 50 / 60Hz |
Frequency range | 40 ÷ 72 Hz |
THDi | <3% |
Input power factor | >0,99 |
Output | |
Nominal voltage | 208 / 220 / 230 / 240 Vac |
Power factor | 1 |
Voltge regulation static/dynamic | ±1% / ±3% |
Nominal frequency | 50 / 60 ± 0,05 Hz |
Overloads capability | 110% - 10min., 130% - 1min., >130% - 1s. |
Efficiency in OnLine mode | >95% |
Efficiency in ECO mode | >99% |
Crest factor | 3:1 |
Switching time | 0ms |
Output sockets | Connection terminals |
Batteries | |
Cold start | Yes |
Nominal voltage | 240Vdc |
Charger curent | 1÷4A |
Charging time | 3 – 8 hours up to 90% capacity (configurable) |
Charging cycle | According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control. |
Dimensions and weights | |
Dimensions (S x G x W) | 438 x 665 x 133 (3U) |
Weight | 17,0 kg |
Signaling and communication ports | |
Operating status indicator | LCD + audible alarm |
Communication | RS232, USB, EPO, slot SNMP, EMBS |
Environmental conditions | |
Noise level | <50 dB |
Operating temperature for UPS | 0°C ÷ 45°C |
Recommended operating temperature | 15°C ÷ 25°C |
Storage temperature | -25°C ÷ 55°C |
Humidity | 0 ÷ 95% (non-condensing) |
Cerifications | |
Interference immunity | EN 62040-2: 2016, EMC CE |
Safety | EN 62040-1: 2017, EN 62040-3: 2011, LVD, CE |
Environmental compatibility | EN IEC 63000: 2018, EN 62321, RoHS |
Optional accesories | |
- SNMP card | |
- RS485 card (Modbus) | |
- AS 400 mini (dry-contact) card | |
- Environmental sensor (EMD) | |
- Rail kits for Rack 19'' (Rail kit) | |
- Remote Emergency Power Off button | |
- External battery modules (EBM) |
Due to constant product improvement all specifications are subject to change without notice.
- Apparent power [kVA]
- 6
- Active power [kW]
- 6
- Technology:
- VFI-SS-111 (OnLine DoubleConversion)
- Phase In/Out:
- 1:1
- Output PF:
- 1
Related Products ( 16 other products in the same category )