Battery module CORE EBM2
Battery module for CORE ONE 2K power supply (no battery). Rack/Tower (2U) cabinet. Possibility to install 2 x 4pcs x 9Ah batteries.
12-CORE-0024
BACKUP TIME
UPS autonomy depending on the number of battery modules
| EBM CORE 2K | Load | Backup time [min] |
| CORE ONE 2K | ||
| UPS + 1xEBM (3 x 4 x 9Ah) | 100% | 19 |
| 75% | 28 | |
| 50% | 46 | |
| 25% | 128 | |
| UPS + 2xEBMs (5 x 4 x 9Ah) | 100% | 38 |
| 75% | 52 | |
| 50% | 88 | |
| 25% | 201 | |
| UPS + 3xEBMs (7 x 4 x 9Ah) | 100% | 55 |
| 75% | 77 | |
| 50% | 148 | |
| 25% | 321 |
TECHNICAL SPECIFICATIONS
| Model | EBM CORE 2K |
| Dedicated for | UPS CORE ONE 2K |
| Type | External battery module |
| Installation method | Rack/Tower |
| Batteries | |
| Nominal voltage | 48 Vdc |
| Max quantity of batteries | 2 x 4pcs x 9Ah |
| Dimensions and weight | |
| Dimensions (S x G x W) | 438 x 510 x 88 (2U) |
| Weight | 28,5 kg |
| Environmenta conditions | |
| Operating temperature for UPS | 0°C ÷ 45°C |
| Recommended operating temperature | 15 °C ÷ 25 °C |
| Storage temperature | -25°C ÷ 45°C |
| Humidity | 0 ÷ 95% (non-condensing) |
| Standard equipment | |
| - Cable between EBM - UPS | |
| - Tower mounting feet | |
| - Ears for Rack mount | |
| - Battery breaker | |
| Optional equipment | |
| - Batteries 9Ah | |
| - Rail kits for Rack 19'' (Rail kit) | |
Due to constant product improvement all specifications are subject to change without notice.
- Max internal batteries
- 8
Related Products ( 10 other products in the same category )